Search Results (2235 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2016-9158 1 Siemens 21 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 314, Simatic S7-300 Cpu 315-2 Dp and 18 more 2025-04-12 N/A
A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions). Specially crafted packets sent to port 80/tcp could cause the affected devices to go into defect mode. A cold restart is required to recover the system.
CVE-2016-9157 1 Siemens 1 Sicam Pas\/pqs 2025-04-12 9.8 Critical
A vulnerability in Siemens SICAM PAS (all versions before V8.09) could allow a remote attacker to cause a Denial of Service condition and potentially lead to unauthenticated remote code execution by sending specially crafted packets to port 19234/TCP.
CVE-2016-9156 1 Siemens 1 Sicam Pas\/pqs 2025-04-12 7.3 High
A vulnerability in Siemens SICAM PAS (all versions before V8.09) could allow a remote attacker to upload, download, or delete files in certain parts of the file system by sending specially crafted packets to port 19235/TCP.
CVE-2016-9155 1 Siemens 30 Ccid1445-dn18, Ccid1445-dn18 Firmware, Ccid1445-dn28 and 27 more 2025-04-12 N/A
The following SIEMENS branded IP Camera Models CCMW3025, CVMW3025-IR, CFMW3025 prior to version 1.41_SP18_S1; CCPW3025, CCPW5025 prior to version 0.1.73_S1; CCMD3025-DN18 prior to version v1.394_S1; CCID1445-DN18, CCID1445-DN28, CCID1145-DN36, CFIS1425, CCIS1425, CFMS2025, CCMS2025, CVMS2025-IR, CFMW1025, CCMW1025 prior to version v2635_SP1 could allow an attacker with network access to the web server to obtain administrative credentials under certain circumstances.
CVE-2016-9154 1 Siemens 12 Desigo Web Module Pxa30-w0, Desigo Web Module Pxa30-w0 Firmware, Desigo Web Module Pxa30-w1 and 9 more 2025-04-12 N/A
Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key.
CVE-2016-4956 6 Novell, Ntp, Opensuse and 3 more 11 Suse Manager, Ntp, Leap and 8 more 2025-04-12 5.3 Medium
ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (interleaved-mode transition and time change) via a spoofed broadcast packet. NOTE: this vulnerability exists because of an incomplete fix for CVE-2016-1548.
CVE-2016-8673 1 Siemens 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more 2025-04-12 N/A
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server at port 80/TCP or port 443/TCP of the affected devices could allow remote attackers to perform actions with the permissions of an authenticated user, provided the targeted user has an active session and is induced to trigger the malicious request.
CVE-2016-8672 1 Siemens 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more 2025-04-12 N/A
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server delivers cookies without the "secure" flag. Modern browsers interpreting the flag would mitigate potential data leakage in case of clear text transmission.
CVE-2016-4954 5 Ntp, Opensuse, Oracle and 2 more 15 Ntp, Leap, Opensuse and 12 more 2025-04-12 7.5 High
The process_packet function in ntp_proto.c in ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (peer-variable modification) by sending spoofed packets from many source IP addresses in a certain scenario, as demonstrated by triggering an incorrect leap indication.
CVE-2016-8565 1 Siemens 1 Automation License Manager 2025-04-12 N/A
Siemens Automation License Manager (ALM) before 5.3 SP3 allows remote attackers to write to files, rename files, create directories, or delete directories via crafted packets.
CVE-2016-8564 1 Siemens 1 Automation License Manager 2025-04-12 N/A
SQL injection vulnerability in Siemens Automation License Manager (ALM) before 5.3 SP3 Update 1 allows remote attackers to execute arbitrary SQL commands via crafted traffic to TCP port 4410.
CVE-2016-8563 1 Siemens 1 Automation License Manager 2025-04-12 N/A
Siemens Automation License Manager (ALM) before 5.3 SP3 Update 1 allows remote attackers to cause a denial of service (ALM service outage) via crafted packets to TCP port 4410.
CVE-2016-8561 1 Siemens 2 Simatic Cp 1543-1, Simatic Cp 1543-1 Firmware 2025-04-12 N/A
A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Users with elevated privileges to TIA-Portal and project data on the engineering station could possibly get privileged access on affected devices.
CVE-2016-7960 1 Siemens 1 Simatic Step 7 2025-04-12 N/A
Siemens SIMATIC STEP 7 (TIA Portal) before 14 uses an improper format for managing TIA project files during version updates, which makes it easier for local users to obtain sensitive configuration information via unspecified vectors.
CVE-2016-7959 1 Siemens 1 Simatic Step 7 2025-04-12 N/A
Siemens SIMATIC STEP 7 (TIA Portal) before 14 improperly stores pre-shared key data in TIA project files, which makes it easier for local users to obtain sensitive information by leveraging access to a file and conducting a brute-force attack.
CVE-2016-7114 1 Siemens 2 En100 Ethernet Module, En100 Ethernet Module Firmware 2025-04-12 N/A
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.87; SIPROTEC 7UT686 : All versions < V 4.02; SIPROTEC 7SD686 : All versions < V 4.05; SIPROTEC 7SJ66 : All versions < V 4.30. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations. A legitimate user must be logged into the web interface for the attack to be successful.
CVE-2016-7113 1 Siemens 2 En100 Ethernet Module, En100 Ethernet Module Firmware 2025-04-12 N/A
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 80/tcp could cause the affected device to go into defect mode.
CVE-2016-7112 1 Siemens 2 En100 Ethernet Module, En100 Ethernet Module Firmware 2025-04-12 N/A
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations.
CVE-2016-7090 1 Siemens 4 Scalance M-800, Scalance M-800 Firmware, Scalance S615 and 1 more 2025-04-12 N/A
The integrated web server on Siemens SCALANCE M-800 and S615 modules with firmware before 4.02 does not set the secure flag for the session cookie in an https session, which makes it easier for remote attackers to capture this cookie by intercepting its transmission within an http session.
CVE-2016-6486 1 Siemens 1 Sinema Server 2025-04-12 N/A
Siemens SINEMA Server uses weak permissions for the application folder, which allows local users to gain privileges via unspecified vectors.